Transformers

       

Transformers

Model: Transformers
Application:

FILM/TV/EVENTS

Quick Reference Guide

KW KVA AMPS AMPS@3Ø AMPS@3Ø
    120V* 208V 480V
30 37 300 104 45
40 50 400 139 60
50 62 500 173 76
60 75 600 208 91
75 93 750 261 113
80 100 800 278 120
100 125 1000 347 150
125 156 1200 433 188
150 187 1400 520 225
175 219 1500 608 264
200 250 1800 694 301
250 312 2400 866 376
300 375 3000 1040 451
400 500 4000 1390 602
500 625 5000 1735

752

*Total Load at 120 Volts.

Voltage Drop - Rule of Thumb

4/0 - 1 Volt per 100 amps per 100 feet
2/0 - 1.5  Volts per 100 amps per 100 feet
#2  - 3 Volts per 100 amps per 100 feet

 